5 Frequency inverter settings

19

Parameter

Setting value / Description / Note

Comments

P482

.. - 01

...

.. - 10

Standardisation of bus I/O Out bits

-400 … 400 %

[ 100 ]

Adjustment of the limit values of the relay functions/Bus Out Bits. For a negative value, the output
function will be output negative.

When the limit value is reached and the setting values are positive, the relay contact closes, with
negative setting values the relay contact opens.

P483

.. - 01

...

.. - 10

Hysteresis of bus I/O Out bits

1 … 100 %

[ 10 ]

Difference between switch-on and switch-off point to prevent oscillation of the output signal.

5.1.2

Additional parameters

Parameter

Setting value / Description / Note

Comments

P507 PPO

type

1 ... 4

[ 1 ]

Only with the Profibus, InterBus or DeviceNet option

1 = PPO- type 1: DeviceNet with data length of 2 words / AC profile 1

2 = PPO- type 2: DeviceNet with data length of 4 words / AC profile 2

3, 4 = PPO- type 3, 4: Reserved

P509

Interface

SK 300E, SK 700E, SK 750E

0 ... 21

[ 0 ]

Selection of the interface from which the inverter is controlled.

0 = Control terminal or keyboard control with the Control Box (option) ,the ParameterBox

(option) or the Potentiometer option

1 = Control terminals only, the inverter can only be controlled via the digital inputs and the

analog input (s).

18 = DeviceNet setpoint

,

the frequency setpoint is transferred via DeviceNet. Control via the

digital inputs is still active.

19 = DeviceNet control word, the control signals (enable, direction of rotation, ...) are transferred

via DeviceNet, the setpoint via the analog input or the fixed frequency.

20 = DeviceNet, all control data is transferred via DeviceNet. The analog input and the digital

inputs have no function (except safety functions, see below)

P509

Control word source

SK 500E

0 ... 10

[ 0 ]

Selection of the interface via which the FI is controlled.

0 = Control terminal or keyboard control with the Control Box (if P510=0), the

ParameterBox (not extension parameter box) or via BUS I/O Bits.

1 = Only control terminals , the FI can only be controlled via the digital and analog inputs or

via the bus I/O Bits.

2 = USS

, the control signals (enable, rotation direction, etc.) are transferred via the RS485

interface, the setpoint via the analog input or the fixed frequencies.

3 = CAN control word

4 = Profibus control word

5 = InterBus control word

6 = CANopen control word

7 = DeviceNet control word

8 = EtherCAT control word

9 = CAN

Broadcast

10 = CANopen Broadcast