7.2 Error messages

Table of possible bus-specific error messages

Display

in the ControlBox

Group

Details in
P700 / P701

Fault

Text in the ParameterBox

Cause

•

Remedy

10.0 Telegram

downtime

Data transfer is faulty. Check P513.

•

Check external Bus connection.

•

Check bus protocol program process.

•

Check Bus Master.

10.2

External bus module
telegram timeout

Telegram transfer is faulty.

•

Check external connection.

•

Check bus protocol program process.

•

Check Bus Master.

10.4

External bus module
initialisation failure

• Check

P746.

•

Bus module not correctly plugged in.

•

Check Bus module current supply.

10.1

10.3

10.5

10.6

10.7

External Bus module system
failure

Further details can be found in Section 5.2 .

E010

10.8 External

module

communication failure

Connection fault / error in the external component