7.2 Error messages

Table of possible bus-specific error messages

Display

in the ControlBox

Group

Details in
P700 / P701

Fault

Text in the ParameterBox

Cause

Remedy

10.0 Telegram

downtime

Data transfer is faulty. Check P513.

Check external Bus connection.

Check bus protocol program process.

Check Bus Master.

10.2

External bus module
telegram timeout

Telegram transfer is faulty.

Check external connection.

Check bus protocol program process.

Check Bus Master.

10.4

External bus module
initialisation failure

• Check

P746.

Bus module not correctly plugged in.

Check Bus module current supply.

10.1

10.3

10.5

10.6

10.7

External Bus module system
failure

Further details can be found in Section 5.2 .

E010

10.8 External

module

communication failure

Connection fault / error in the external component