2 second and third setpoint sk 500e (sw2/3) – NORD Drivesystems BU0080 User Manual

Page 34

Advertising
background image

NORDAC DeviceNet Manual

34

BU

0080

GB

6.4.6.2

Second and third setpoint SK 500E (SW2/3)

In addition to setpoint 1, a second setpoint can be transferred in word PZD3 and a third setpoint in PZD4.

PZD1 PZD2 PZD3 PZD4

STW

SW1

SW2

SW3

The second and third setpoints are always 16 Bit. The function of the second and third setpoints can be set in
the inverter with parameter P547 ‘Setpoint 2 function’ and P548 ‘Setpoint 3 function’ respectively.

Both setpoints are transferred as whole numbers in the range -32768 to 32767. The value 16384 (4000 HEX)
corresponds to 100%. The value C000 HEX is equal to –100%, so setpoints in the range –200% to +200% can
be transferred. A setpoint of 100% corresponds to the respective nominal value:

Setting

100% is equal to

Off

Setpoint frequency, actual frequency PID, actual
frequency PID limited, actual frequency PID monitored,
frequency addition, frequency subtraction, maximum
frequency

Maximum frequency (P105)

Torque current limit

Torque current limit (P112)

Current limit

Inverter nominal current

Servo mode torque

Nominal torque (P112)

Lead torque

Lead torque (P214)