3 control word (stw) – NORD Drivesystems BU0080 User Manual

Page 29

Advertising
background image

6 Data transmission

29

6.4.3

Control word (STW)

.4.3

Control word (STW)

The control word (STW) is the first word transferred to the frequency inverter in the process data area in an
order telegram. For example, a control word "Ready for switch-on" corresponds to 047E

(hex)

.

The control word (STW) is the first word transferred to the frequency inverter in the process data area in an
order telegram. For example, a control word "Ready for switch-on" corresponds to 047E

(hex)

.

PZD1

PZD1 PZD2

PZD2 PZD3

PZD3 PZD4

PZD4

STW SW1 SW2/3

SW2/3

15 14

13 12 11 10

9

8

7

6

5

4

3

2

1

0

Bit

Value

Significance

Comments

0

0

OFF 1

Reverse with the brake ramp, with disconnection from supply at f=0Hz

1

ON

Ready for operation

1 0

OFF

2

Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is disabled.

1 Operating

condition

OFF 2 is cancelled

2 0

OFF

3

Quick stop with programmed quick stop time; with disconnection from supply at
f=0Hz; the FI switches to starting disabled condition.

1 Operating

condition

OFF 3 is cancelled

3 0

Disable

operation

Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is enabled.

1

Enable operation

The output voltage is enabled; ramp to the existing setpoint

4

0

Lock ramp generator

Ramp generator is set to zero; no disconnection from supply at f=0Hz; FI
remains in the operation enabled state.

1 Operating

condition Enable ramp generator

5

0

Stop ramp generator

The setpoint currently provided by the ramp generator is "frozen" (frequency is
maintained).

1

Enable ramp generator

Enable setpoint on ramp generator

6

0

Disable setpoint

Selected setpoint value is set to zero on the ramp generator.

1

Enable setpoint

Selected ramp generator setpoint is activated.

7 0

No

acknowledgement With the switch from 0 to 1, errors which are no longer active are

acknowledged.

1 Acknowledge

Note: When a digital input has been programmed for the "ack.fault" function,
this bit must not permanently be set to 1 via the bus (otherwise, edge
evaluation would be prevented).

8 0

1

Bit 8 active

Bus bit 8 from the control word is set. (Only for SK 200E and SK 500E)
For further details of the function please refer to parameter (P480).

9 0

1

Bit 9 active

Bus bit 9 from the control word is set. (Only for SK 200E and SK 500E)
For further details of the function please refer to parameter (P480).

10

0

PZD invalid

The transmitted process data is invalid.

1

PZD valid

Valid process data is transferred from the master.
Note:If setpoints only are transferred via the bus, this bit must be set so that
the transferred setpoint is valid.

11 0

1 Rotational

direction:

right

Rotational direction right (priority) – ON*

12 0

1 Rotational

direction:

left

Rotational direction left – ON*

13 0/1

Reserved

14 0/1 Bit 0 to switch parameter

set

15 0/1 Bit 1 to switch parameter

set

00 = Parameter set 1
01 = Parameter set 2

10 = Parameter set 3
11 = Parameter set 4

* If Bit 12=0, then "Direction of rotation right ON" applies