NORDAC DeviceNet Manual

42

BU

0080

GB

6.5.9

Class 100-107 (64

hex

-6B

hex

) – NORDAC Objects

All parameters of the frequency inverter can be accessed with the aid of the NORDAC Objects. The parameter
number (PNr) can be obtained from the operating instructions for the frequency inverter:

Conversion of PNr

→ to class:

Area

Conversion of Class

→ to PNr:

Class = 100 + PNr / 100

(100-109)

PNr = (Class – 100) * 100 + Attribute

Attribute = PNr % 100

(0-99)

Sub-Index = Instance -1

Instance = Sub-Index +1

(1-255)

E.g.: P745, Sub-Index 2 = Class 107, Attribute 45, Instance 3

Class

Inst Attr.

Description

Type

Access

100

NORDAC Operation

1-255 0-99 Operating displays

101

NORDAC Basic

1-255 0-99 Basic parameters

102

NORDAC Motor

1-255 0-99 Motor data

103

NORDAC Control

1-255 0-99 Control parameters

104

NORDAC Terminal

1-255 0-99 Control terminal settings

105

NORDAC Additional

1-255 0-99 Additional functions

106

NORDAC Positioning

1-255 0-99 Positioning parameters

107

NORDAC Information

1-255 0-99 Information parameters

6.5.10

Class 120 (78

hex

) – NORDAC Index Object

All parameters can be accessed via this object by setting the parameter number and the sub-index. Then the
parameter can be read or written via Attribute 3.

Inst Attr.

Description

Type

Access

1 Parameter

number

UINT

Get/Set

2 Parameter

sub-index

USINT

Get/Set

1

3

Read / Write parameter

DINT

Get/Set