2 module status – NORD Drivesystems BU0080 User Manual

Page 25

Advertising
background image

5 Frequency inverter settings

25

Parameter

Setting value / Description / Note

Comments

P745

... - 01

... - 03

Module version

SK 700E, SK 750E

0.0 ... 3276.7

Software version of the installed module

[01]

Technology

unit

(E.g.:

DeviceNet

Technology

Unit)

[02]

Customer

Unit

[03] Special Extension Unit

P746 Module

status

SK 300E, SK 500E

0000 ... FFFF (hex)

Indicates the actual status (readiness, error, communication) of the technology unit (SK TU2/3-
xxx), but only when own processor is present, therefore not for the SK TU2/3-CTR.

Code details can be found in the respective BUS module manual. Different contents are shown
depending on the modules. (DeviceNet: See Section 5.2 )

P746

... - 01

... - 03

Module status

SK 700E, SK 750E

0000 ... FFFF (hex)

Status of integrated modules

[01] Technology unit

(E.g.: DeviceNet Technology Unit)

[02]

Customer

Unit

[03] Special Extension Unit

NOTE

When activated, the functions block current, quick stop, remote control and cancel error
are available at the (local) control terminals. To operate the drive, a high signal must be present
on the digital inputs being used before the drive can be enabled.

5.2 Module status

In parameter P746, the status of the DeviceNet module can be read.

Parameter P746 is a subindex parameter: Subindex 0 contains the status of the DeviceNet technology unit.
The parameter contains binary coded information which is displayed in hexadecimals:

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

Module ID

DeviceNet=0E

hex

Module ready

Module in status “operational”

E.g.: 0E03

hex

= DeviceNet module, module

ready and operational

Initialisation active

Reserved (0)

Module error

Timeout error

Initialisation error

Reserved (0)