5 Frequency inverter settings

23

5.1.3

Information parameters

NOTE

As of firmware version V1.9 R0 for the SK 500E series, not only current error messages but
also warnings and information messages can be displayed via the parameter. In this context,
the parameter (P700) has been converted into an array parameter. I.e. error messages are
displayed in (P700 [-01]), warnings in (P700[-02]), and information in (P700 [-03]).

For all other series (SK 300E, SK 700E, SK 750E), parameter (P700) still only indicates error
messages.

Parameter

Setting value / Description / Note

Comments

P740

... - 01

... - 06

Process data bus In

SK 300E, SK 700E, SK 750E

0000 ... FFFF (hex)

Displays the actual control word and the setpoints.

... - 01 = Control word

... - 02 = Setpoint 1 (P546)

... - 03 = Setpoint 1 High byte

... - 04 = Setpoint 2 (P547)

... - 05 = Setpoint 3 (P548)

... - 06 = Bus I/O In Bits (P480)

P740

... - 01

... - 13

Process data bus In

SK 500E

... - 01 = Control word...

Control word, source from
P509.


-

This parameter informs about
the actual control word and
the setpoints that are
transferred via the bus
systems.

- 02 = Setpoint 1

03 = Setpoint 2

... - 04 = Setpoint 3

Setpoint data from main
setpoint P510 - 01.

... - 05 = Bus I/O Out Bits (P480)

The displayed value depicts
all Bus In bit sources linked
with OR.

… - 06 = Parameter data Out 1
... - 07 = Parameter data In 2
... - 08 = Parameter data In 3
... - 09 = Parameter data In 4
... - 10 = Parameter data In 5

Data during parameter
transfer.

0000 ... FFFF (hex)

… - 11 = Setpoint 1
... - 12 = Setpoint 2
... - 13 = Setpoint 3

Setpoint data from auxiliary
setpoint P510 - 02.

P741

... - 01

... - 06

Process data bus Out

SK 300E, SK 700E, SK 750E

0000 ... FFFF (hex)

Displays the actual status word and actual values.

... - 01 = Status word

... - 02 = Actual value 1 (P543)

... - 03 = Actual value 1 High byte

... - 04 = Actual value 2 (P544)

... - 05 = Actual value 3 (P545)

... - 06 = Bus I/O In Bits (P481)