NORD Drivesystems BU0090 User Manual
Page 37

4 Frequency inverters - settings and control elements
BU 0090 GB
37
4.1.3
Information parameters
Parameter
Setting value / Description / Note
Comments
P740
... - 01
…
... - 06
Process data bus In
SK 300E, SK 700E, SK 750E
0000 ... FFFF (hex)
Displays the actual control word and the setpoints.
... - 01
= Control word
... - 02
= Setpoint 1 (P546)
... - 03
= Setpoint 1 High byte
... - 04
= Setpoint 2 (P547)
... - 05
= Setpoint 3 (P548)
... - 06
= Bus I/O In Bits (P480)
P740
... - 01
…
... - 13
Process data bus In
SK 500E
... - 01 =
Control word...
Control word, source from P509.
... - 02 =
Setpoint 1
... - 03 =
Setpoint 2
... - 04 =
Setpoint 3
Setpoint data from main
setpoint P510 - 01.
... - 05 =
Bus I/O Out Bits (P480)
The displayed value depicts
all Bus In bit sources linked
with OR.
... - 06 =
Parameter data In 1
... - 07 =
Parameter data In 2
... - 08 =
Parameter data In 3
... - 09 =
Parameter data In 4
... - 10 =
Parameter data In 5
Data during parameter
transfer.
0000 ... FFFF (hex)
This parameter informs
about the actual control
word and the setpoints that
are transferred via the bus
systems.
... - 11 =
Setpoint 1
... - 12 =
Setpoint 2
... - 13 =
Setpoint 3
Setpoint data from auxiliary
setpoint
P510 -02.
P741
... - 01
…
... - 06
Process data bus Out
SK 300E, SK 700E, SK 750E
0000 ... FFFF (hex)
Displays the actual status word and actual values.
... - 01
= Status word
... - 02
= Actual value 1 (P543)
... - 03
= Actual value 1 High byte
... - 04
= Actual value 2 (P544)
... - 05
= Actual value 3 (P545)
... - 06
= Bus I/O In Bits (P481)
P741
... - 01
…
... - 13
Process data bus Out
SK 500E
... - 01 =
Status word
Status word, source from P509.
... - 02 =
Actual value 1 (P543)
... - 03 =
Actual value 2 (P544)
... - 04 =
Actual value 3 (P545)
... - 05 =
Bus I/O Out Bits (P481)
The displayed value depicts
all Bus In bit sources linked
with OR.
... - 06 =
Parameter data Out 1
... - 07 =
Parameter data Out 2
... - 08 =
Parameter data Out 3
... - 09 =
Parameter data Out 4
... - 10 =
Parameter data Out 5
Data during parameter
transfer.
0000 ... FFFF (hex)
This parameter provides
information about the actual
status word and the actual
values that are transferred
via the bus systems.
... - 11 =
Master function actual value 1
... - 12 =
Master function actual value 2
... - 13 =
Master function actual value 3
Actual value of master
function
P502/P503.