6 Examples

BU 0090 GB

61

Example for the writing of a parameter (PKW data via USS protocol / Parameter string):
For example, in order to set the release time of the brake P114 (parameter number PNU = 114 / 72

hex

) of the

FI to 1 sec for parameter set 1, proceed as follows:

• Select parameter label PKE (AK =1 for change parameter value (word) and parameter number

PNU = 72

hex

)

• Taking the internal resolution of the frequency inverter into account (0.01sec) => for 1 sec there

must be a parameter value PWE of 1 / 0.01 = 100

dec

(64

hex

)

• Select parameter set 1 (IND = 0)
• Select order label 2 = change parameter value (word)
• Check response telegram (Read Parameter String)

The command Write Parameter String must be transferred with the following parameter Bytes DBB04 to
DBB16 and the corresponding parameter values:

Data Byte
in DB13

Value in
hex

Meaning / Note

DBB4

40

Write the command number for the parameter string

DBB5

01

Slave address

DBB6

0A

Number of parameter bytes, 0A

hex

corresponds to 10

dec

DBB7

00

Byte 0: Index

DBB8

02

Byte 1: Index PKW data

DBB9

20

Byte 2: parameter label PKE, order label 2 for change parameter value

DBB10

72

Byte 3: parameter label PKE, parameter number PNU

DBB11

00

Byte 4: Sub-index IND

DBB12

00

Byte 5: Sub-index IND, taking into account parameter set 1 = IND 0

DBB13

00

Byte 6: parameter value PWE1

DBB14

00

Byte 7: parameter value PWE1

DBB15

00

Byte 8: parameter value PWE2

DBB16

64

Byte 9: parameter value PWE2, 1sec corresponds to 64

hex


With this, the brake release time in P114 for parameter set 1 is changed to 1.00s.