2 module status – NORD Drivesystems BU0090 User Manual

Page 39

Advertising
background image

4 Frequency inverters - settings and control elements

BU 0090 GB

39

Parameter

Setting value / Description / Note

Comments

P746 Module

status

SK 300E, SK 500E

0000 ... FFFF (hex)

Indicates the actual status (readiness, error, communication) of the technology unit
(SK TU2/3-xxx), but only when own processor is present, therefore not for the SK TU2/3-CTR.

Code details can be found in the respective BUS module manual. Different contents are shown
depending on the modules. (AS interface: See Section 4.2)

P746

... - 01

... - 03

Module status

SK 700E, SK 750E

0000 ... FFFF (hex)

Status of integrated modules

[01] Technology unit

(E.g.: AS interface Technology Unit)

[02]

Customer

Unit

[03] Special Extension Unit


NOTE

When activated, the functions block current, quick stop, remote control and cancel error
are available at the (local) control terminals. To operate the drive, a high signal must be present
on the digital inputs being used before the drive can be enabled.

4.2 Module status

The status of the AS interface module can be read out in parameter P746.
Parameter P746 is a subindex parameter: Subindex 0 contains the status of the AS interface technology unit.
The parameter contains binary coded information which is displayed in hexadecimal:

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Module ID

AS Interface=09

hex

Module ready

Module in status “operational”

E.g.: 0903

hex

= AS module, module ready and

operational

Initialisation active

AS i type

(0= Standard; 1=A/B Slave)

Module error

Timeout error

Initialisation error

Reserved (0)