NORDAC AS-Interface Manual

64

BU

0090

GB

Parameterisation of functions:

Only the parameters relevant for the function of the I/Os are listed here. For further information, please refer to
the manuals BU0500 and BU0510.

Parameter / Array

Input and Output

Setting / Function

P420 digital input 1

DIN1 / digital input 1

01 = Enable right

P421 digital input 2

DIN2 / digital input 2

02 = Enable left

P422 digital input 3

DIN3 / digital input 3

08 = parameter set switch-over Bit 0

P423 digital input 4

DIN4 / digital input 4

17 = parameter set switch-over Bit 1

P424 digital input 5

DIN5 / digital input 5

13 = PTC input

P425 digital input 6

DIN6 / digital input 6

22 = Error acknowledgement

P470 digital input 7

DIN7 / digital input 7

23 = Reference point

P480 [05] Bus IO In Bit 4

Sensor input Dig In 1

55 = Bit 0 position (increment) array

P480 [06] Bus IO In Bit 5

Sensor input Dig In 2

56 = Bit 1 position (increment) array

P480 [07] Bus IO In Bit 6

Sensor input Dig In 3

57 = Bit 2 position (increment) array

P480 [08] Bus IO In Bit 7

Sensor input Dig In 4

58 = Bit 3 position (increment) array

P434 function output 1

Relay contact K1

1 = External brake

P441 function output 2

Relay contact K2

7 = Error

P450 function output 3

DOUT 1

3 = Current limit

P455 function output 4

DOUT 2

4 = Torque current limit

P481 [05] Bus IO Out Bit 5

Actuator output Dig Out 1

20 = Reference point

P481 [06] Bus IO Out Bit 6

Actuator output Dig Out 2

21 = Position reached

P509 interface

0 = Control terminals or keyboard

P543 Bus actual value 1

8

12 = Bus IO Out Bits 0…7

P546 Bus setpoint 1

9

17 = Bus IO Bits 0…7

The signal statuses of the I/O are only virtually displayed via the digital I/O LEDs with the SK TU1-AS1 and
SK TU3-AS1 AS interface modules. No I/O LEDs are available for the SK TU2-ASx modules.
In order to check the signal statuses of the IOs, the status can be checked via the information parameters
P7xx. The relevant array must be selected in the corresponding information parameter. The sensor inputs or
Bus IO In Bits are displayed in parameter P740 / process data Bus In.

The sensor inputs or Bus IO Out Bits are displayed in parameter P741 / process data Bus Out.



8

One of the three actual Bus values in parameters P543 to P545 must be parameterised on Bus IO Out Bits 0…7.

9

One of the three Bus setpoint values in parameters P546 to P548 must be parameterised on Bus IO Out Bits 0…7.