6 Examples

BU 0090 GB

59


With this, the start-up time in P102 for parameter set 1 is changed to 10.00s.

If the start-up time for all 4 parameter sets is to be changed at the same time, this can also be carried out with
only one Write Parameter String command. For this, the number of parameter Bytes must be increased to 10
and the corresponding parameter values entered in DBB11 to DBB16.


With this the different start-up times P102 for the 4 parameter sets are parameterised with the following values:

Parameter set 1

03E8 => 10.00s

Parameter set 2

07D0 => 20.00s

Parameter set 3

0BB8 => 30.00s

Parameter set 4

0FA0 => 40.00s


For array parameters (e.g. P480 to P483) all 8 arrays can be changed or executed with only a single Write
Parameter String command. For this, the number of parameter Bytes must be increased to 18 and the
corresponding parameter values entered in DBB17 to DBB24.

Data Byte in DB13

Value in hex

Meaning / Note

DBB4

40

Write the command number for the parameter string

DBB5 01

Slave

address

DBB6

04

Number of parameter Bytes, 04

hex

DBB7

00

Byte 0: Index

DBB8

54

Byte 1: Index, start-up time P102, parameter set 1

DBB9

03

Byte 2: parameter value, taking the resolution 0.01 into account

DBB10

E8

Byte 3: parameter value, taking the resolution 0.01 into account

Data Byte
in DB13

Value in
hex

Meaning / Note

DBB4

40

Write the command number for the parameter string

DBB5

01

Slave address

DBB6

0A

Number of parameter bytes, 0A

hex

corresponds to 10

dec

DBB7

00

Byte 0: Index

DBB8

54

Byte 1: Index, start-up time P102, parameter set 1

DBB9

03

Byte 2: parameter value of parameter set 1, taking the resolution of 0.01 into account

DBB10

E8

Byte 3: parameter value of parameter set 1, taking the resolution of 0.01 into account

DBB11

07

Byte 4: parameter value of parameter set 2, taking the resolution of 0.01 into account

DBB12

D0

Byte 5: parameter value of parameter set 2, taking the resolution of 0.01 into account

DBB13

0B

Byte 6: parameter value of parameter set 3, taking the resolution of 0.01 into account

DBB14

B8

Byte 7: parameter value of parameter set 3, taking the resolution of 0.01 into account

DBB15

0F

Byte 8: parameter value of parameter set 4, taking the resolution of 0.01 into account

DBB16

A0

Byte 9: parameter value of parameter set 4, taking the resolution of 0.01 into account