NORDAC AS-Interface Manual

52

BU

0090

GB

The following table lists all the orders which can be transferred from the master to the inverter. The right-hand
column contains the response, which is normally sent (response label positive). Only certain response labels
are possible, depending on the order label. In case of error (response label negative) the inverter will always
supply the value 7 in the response label (AK) to the master.

AK

Function

Response label positive

0 No

order

0

1

Order parameter value

1 / 2

2

Change parameter value (word)

1

3

Change parameter value (double word)

2

4

Reserved

-

5

Reserved

-

6

Order parameter value (array)

4 / 5

7

Change parameter value (array word)

4

8

Change parameter value (array double word)

5

9

Order the number of array elements

6

10 Reserved

-

11

Change parameter value (array double word)

without writing into EEPROM

5

12

Change parameter value (array word)

without writing into EEPROM

4

13

Change parameter value (double word)

without writing into EEPROM

2

14

Change parameter value (word)

without writing into EEPROM

1

Meaning of the values sent in the response label:

AK

Function

0 No

response

1

Transfer parameter value (word)

2

Transfer parameter value (double word)*

4

Transfer parameter value (array word)

5

Transfer parameter value (array double word)*

7

Order cannot be executed (with error number in PWE2)

*Only possible with 4 words


As long as an order has not yet been executed, the inverter provides the response to the last order. Therefore
the master must always check whether the received response matches the order sent.

For the plausibility check, the value in the response label (AK), the received parameter number (PNU) with the
corresponding Index (IND) as well as the current parameter value (PWE) can be used for the description of
parameters.