NORDAC AS-Interface Manual

46

BU

0090

GB

Examples of direct parameters:
Writing the parameter P102 start-up time with value 1s (with 0.01 resolution 100

dec

= 64

hex

)

-00 54 00 64

(2 words) transferred as a Write order


Writing the functions in parameter P480 for BusIO In Bits 0 and 1
(Bit 0: enable right = 1; Bit 1: Error acknowledgement = 12)
-00 6C 00 01 00 0C (3 words) transferred as a Write order

Reading of parameter P509 interface and P513 telegram down time
-00 8C (1 word) transferred as a Write order
-transfer Read command and evaluate the value for P509, interface
-transfer Read command and evaluate the value for P513, telegram down time

5.3.2

PKW Parameter-String

The data after the index 00 02

hex

correspond to the PKW component of the USS protocol. Further information

regarding the structure and meaning of the individual data words of the parameter range (PKW) is described in
Section 5.5. In principle, all parameters of the frequency inverter can be read and written with this (insofar as
they can be changed).

0 1 2 3 4 5 6 7 8 9

Index

PKW data, 3 or 4 words

0002

hex

PKE

IND

PWE1 PWE2


There are permissible lengths of a total of 4 and 5 words, corresponding to integer (16 Bit) and long (32 Bit)
parameters. Write orders with other lengths are ignored by Index 00 02

hex

. This causes the index to be reset to

00 00

hex

. If a Write order is transferred in order to read a parameter, this must also have the corresponding

length (integer/long). The parameter value for the Read command is only updated once by the frequency
inverter, i.e. if at a later time only the Read command is carried out (without a previous Write order), the
parameter value read is not the current one. If e.g. an information parameter (P7xx) is to be regularly read, this
must always be started with a new Write order and a subsequent Read command.

Examples of PKW parameter strings:
Writing (command of parameter P102 start-up time (P102 = 66

hex

; Subindex = 0; Integer) with the value 1s

(with 0.01 resolution 100

dec

= 64

hex

)

-00 02 20 66

00 00 00 64 (4 words) transferred as a Write order

-perform the Read command repeatedly until the parameter number and the subindex in the order agree. If

these are identical, the response label and the parameter value must be checked.


Reading (order label =1) of the module status parameter (P746 = 2EA

hex

; Subindex = 0; Integer)

-00 02 12 EA

00 00 00 00 (4 words) transferred as a Write order

-perform the Read command repeatedly until the parameter number and the subindex in the order agree. If

these are identical, the response label must be checked. Reading of a current value must be once again
started with a Write order.


Reading (order label = 1) of actual position parameter (P601 = 259

hex

; Subindex = 0; long)

-00 02 12 59

00 00 00 00 00 00 (5 words) transferred as a Write order

-perform the Read command repeatedly until the parameter number and the subindex in the order agree. If

these are identical, the response label must be checked.