3 causes of errors – NORD Drivesystems BU0090 User Manual

Page 67

Advertising
background image

7 Faults

BU 0090 GB

67

7.3 Causes of errors

The following table lists possible causes of errors / error statuses and the procedure for rectifying them:

Error / Status

Possible cause

Course of action

Parameters specific to the
AS interface are not
displayed on the display of
the FI or in NORDCON

The necessary software version of
the FI is not installed.

SK 700E ≥ Version 3.1 Rev.1
SK 750E ≥ Version 3.1 Rev.1
SK 300E ≥ Version 1.6 Rev.3

SK 5xxE

Version 1.3 Rev.1

¾

Check which software version is installed
using parameter P707

¾

An update of the FI software version may be
necessary

¾

For older devices or software versions the FI
must be replaced

Communication to AS
interface module interrupted

Timeout error

Bus cable faulty

Slave address incorrect

No power supply

¾

Check LED status display (See Section 4.3)

¾

Check slave address

¾

Check bus connection and cable

¾

Check parameter P509, interface

¾

Check parameter P746, module status

PWR/FLT LED
and/or
DEVICE S/E LED
are off

No 24V supply

As interface power unit faulty or off

Cable connection interrupted

¾

Check LED status display (See Section 4.3)

¾

Check AS interface power unit

¾

Check cable connection

Signal statuses of sensors
and actuators are not
recognised

Cable connection interrupted

Incorrect connection

Faulty sensor/actuator

¾

Check sensor or actuator connection

¾

Check whether signal status is indicated in
IO LED display (only SK TU1-AS1 and SK
TU3-AS1) (see Section 2.1.2 or 2.2.2)

¾

Check parameter P740 process data Bus
In Bus

¾

Check parameter setting (Bus Out Bits 0…7)
of the actual Bus values (P543 to 545)

¾

Check parameter setting (Bus In Bits 0…7)
of the Bus setpoint values (P546 to 548)

¾

Check 24V (AUX) power supply

AS interface slave not
recognised by AS interface
master

Slave address incorrect

or address 0 (default setting)

Double addressing of slaves

Bus cable / connection interrupted

¾

Check slave address, address ≥1 and ≤ 31

¾

Slave

addressing

¾

Re-address

¾

Check bus connection and cable

PWR/FLT LED
alternate red/green

Peripheral error

¾

Check power supply to FI

¾

Check 24V (AUX) power supply