Figure 2-1. dc power connector -3, Table 2-1. dc connector symbol definitions -3, Figure – ADTRAN MX2800 M13 User Manual

Page 25: Table 2-1, Figure 2-1. dc power connector, Negative side of dc power source (usually –48 vdc), Pwr fail

Advertising
background image

MX2800 M13 Multiplexer User Manual

Installation and Operation, Section 2

61200290L1-1G

2-3

Figure 2-1. DC Power Connector

The following UL requirements must be met during installation of the MX2800 DC version:

1. Disconnect all power sources prior to servicing. Unit may use multiple power sources.

2. Input: Minimum 48 VDC, 0.8 amps

3. Input: Minimum 120 VAC, 0.32 amps

4. Connect to a reliably grounded –48 VDC source which is electrically isolated from the AC source. Use

24 VDC source for 1202289L3.

5. The branch circuit overcurrent protection must be a fuse or circuit breaker rated minimum 48 VDC,

maximum 20 amps.

Table 2-1. DC Connector Symbol Definitions

Symbol

Definition

PWR FAIL

Battery backup connector. If the AC fails, a trap is sent to
alert user when connected to the 4175043L2 battery
backup or equivalent system.

–

Negative side of DC power source (usually –48 VDC)

RET

Positive side of DC power source (usually ground)

Frame Ground

DC POWER

115 AC 50/60Hz

0.8A

PWR

FAIL

+

T

R

S

T

R

CLK

A

CLK

B

S

–

L
A

N

NONCRITICAL

DSX-1/E1

(OUT)

DSX-1/E1

(IN)

NO COM NC

CRITICAL

M
O
D

E

M

OUT

IN

A

B

A

B

DS3/STS-1

PWR

FAIL

+

–

PWR

FAIL

+

USE COPPER

CONDUCT

ORS ONLY!

-48V 0.7A

+24V 1.5A

-48V 0.7A

+24V 1.5A