Operating Instructions Temperature Indicating Controller CF1H

V 1.2

01/2007

- 18 -


SV

(Auto-tuning Cancel)

SV

(Auto-tuning Perform)

[Factory adjusted as Auto-tuning Cancel]


If the Auto-tuning is released during the process,

the PID value reverts to the former value.


Main proportional band setting

Mode to set the proportional band for Main control.

Setting value

Setting range: 0.1 … 999.9 %

[Factory adjusted as 2.5 %]

MODE

When the ON/OFF action is selected in control

action designation (Page 10), this display is not

available.

Cool proportional band setting Mode to set the proportional band for cooling control.

Setting value

Setting range: 0.0 … 10.0

MODE

(Multiplying factor to the main control proportional band value)

[Factory adjusted as 1.0 times (2.5 %)]

This display is not available when the option (code: D 2) is not

applied or when the ON/OFF action is selected in Control action

designation (page 10).


Integral time setting

Mode to set the integral time.

Setting value Setting range: 0 … 3600 s

[Factory adjusted as 200 s]

MODE

Setting the value to 0 disables the function.

This display is not available when the ON/OFF action or

PD action is selected in Control action designation (page 10).


Derivative time setting

Mode to set the derivative time.

Setting value Setting range: 0 … 3600 s

[Factory adjusted as 50 s]

MODE

Setting the value to 0 disables the function.

This display is not available when the ON/OFF action is

selected in Control action designation (page 10).