Operating Instructions Temperature Indicating Controller CF1H

V 1.2

01/2007

- 19 -



Main control

Mode to set the proportional cycle of Main control.

proportional cycle setting

Setting range: 1 … 120 s

Setting value [Factory adjusted as 30 s to Relay contact output

type, and 3 s to Non-contact voltage output type]

MODE

This setting item is not available to Current output type.

When the ON/OFF action is selected in Control action

designation (page 10), this display is not available.


With the Relay contact output type, if the Proportional

cycle time is decreased, the frequency of the relay

action increases, and the life of the relay contact

is

shortened.


Cooling control

Mode to set the proportional cycle of Cooling

proportional

cycle

setting

control.

Setting value Setting range: 1 … 120 s

[Factory adjusted as 30 s for Relay contact output

MODE

type, and 3 s for Non-contact voltage output type]

This display is indicated only when the option [DR2] or [DS2]

is

applied.

When the ON/OFF action is selected in Control action

designation (page 10), this display is not available.


Manual reset setting

Mode to set the reset value to correct the offset

Setting value

(Deviation between SV and PV when equilibrium status).

MODE

Setting range: ± proportional band converted value

However, when TC or RTD input, in the range,

–199.9 … 999.9 °C (°F)

when DC input, in the range,

–1999 … 9999

[Decimal point place follows the selection.]

[Factory adjusted as 0.0 °C]


This display is indicated only when PD action is designated in

the Control action designation (page 10).

Manual reset setting method:

When SV>PV, set the positive + value (SV–PV).

When SV<PV, set the negative – value (SV–PV).