Operating Instructions Temperature Indicating Controller CF1H

V 1.2

01/2007

- 29 -

Alarm 1 (A1) action

Mode to select the action Energized or Deenergized

Energized/Deenergized

for Alarm 1.

Selection

[Factory adjusted as Energized]

MODE

This display is not indicated when the rotary switch is set to No. 0

or No. 7 in Alarm 1 action designation (page 12).


Energized

Deenergized


Alarm 2 (A2) action

Mode to select the action Energized or Deenergized

Energized/Deenergized

for Alarm 2.

Selection

[Factory adjusted as Energized]

MODE

This display is not indicated when the rotary switch is set to No. 0

or No. 7 in Alarm 2 action designation (page 12), or the option

[2AS or 2AL] is not applied.

Selection items: The same as those of the alarm 1 (A1) action

Energized/Deenergized

selection.

Alarm 1 hysteresis setting

Mode to set the hysteresis value for Alarm 1.

Setting value

Setting range: 0.1 … 100.0 °C (for TC, RTD inputs)

1 … 1000 (for DC input)

MODE

(Decimal point place follows the selection.)

[Factory adjusted as 1.0 °C]

This display is not indicated when the rotary switch is set to No. 0

or No. 7 in Alarm 1 action designation (page 12).

Alarm 2 hysteresis setting

Mode to set the hysteresis value for Alarm 2.

Setting value

Setting range: 0.1 … 100.0 °C (for TC, RTD inputs)

1 to 1000 (for DC input)

MODE

(Decimal point place follows the selection.)

[Factory adjusted as 1.0 °C]
This display is not indicated when the option [2AS or 2AL] is not
applied and when the rotary switch is set to No. 0 or No. 7 in Alarm 2
action designation (page 12) even if the option [2AS or 2AL] is
applied.