Operating Instructions Temperature Indicating Controller CF1H

V 1.2

01/2007

- 20 -



Alarm 1 (A1) setting

Mode to set the action point of the Alarm 1 (A1) output.

Setting value

This item is not displayed if setting the rotary switch

MODE

to No. 0 or No. 7 (See page 12.)

Setting range: See [table 4.2-2].

[Factory adjusted as 0 °C]

Alarm 2 (A2) setting

Mode to set the action point of the Alarm 2 (A2) output.

Setting value

This item is not displayed if the option [2AS or 2AL] is not

MODE

applied or even if it is applied, when setting the

rotary switch to No. 0 or No. 7 (See page 12.)

Setting range: See [table 4.2-2].

[Factory adjusted as 0°C]


Setting range of Alarm 1 and 2
(The setting range is the same when the standby function is added.)
[Table 4.2-2]

Alarm type

Setting range

High limit alarm

–Input span to Input span *1

Low limit alarm

–Input span to Input span *1

High/Low limits alarm

0 to Input span *1

High/Low limit range alarm

0 to Input span *1

Process high alarm

Input range minimum to Input range maximum *2

Process low alarm

Input range minimum to Input range maximum *2

For RTD input, the minimum value of the negative side is –199.9.
For DC input, the minimum value of the negative side is –1999. (Decimal point place
follows the selection.)
*1: For DC input, the Input range span is the same as the Input range scaling span.
*2: For DC input, Input range maximum (minimum) is the same as the Input range
scaling maximum (minimum) value.

Heater burnout alarm setting Mode to set the Heater current value for Heater burnout alarm.

Setting value

Setting range: When [W12 or W32] 0.0 … 20.0 A

MODE

(However, the indication is 0.0 … 50.0.)

When [W15 or W35] 0.0 … 50.0 A

[Factory adjusted as 0.0 A]

This display is indicated only when the option [W ] is applied

.



Setting the value to 0.0 disables the function.

It is recommended to set approx. 80 % of the Heater current

value considering the voltage fluctuation.

Self-holding is not available to the alarm output.