Operating Instructions Temperature Indicating Controller CF1H

V 1.2

01/2007

- 32 -


Display selection when

Mode to select the display when the control output is off.

control output is off

Selection

[Factory adjusted as indicating OFF on the PV display]

MODE


OFF is indicated on the PV display.

No indication (all unlit).

Only PV is indicated.

Main setting value

Mode to set the rising rate of the main setting

rising rate setting

value. (Rising value per minute)

Setting value

Setting the value to 0 or 0.0 disables the function.

MODE Setting

range:

0 … 9999 °C/min.

Thermocouple, except T and RTD without

a decimal point

0.0 … 999.9 °C/min. Thermocouple T and RTD with

a decimal point

0 … 9999,

DC input (Decimal point place follows

the

selection.)

[Factory adjusted as 0°C/min.]

Main setting value

Mode to set the falling rate of the main setting

falling rate setting

value. (Falling value per minute)

Setting value

Setting the value to 0 or 0.0 disables the function.

MODE Setting

range:

0 … 9999 °C/min.

Thermocouple, except T and RTD without

a decimal point

0.0 … 999.9 °C/min. Thermocouple T and RTD with

a decimal point

0 … 9999

DC input (Decimal point place follows

the

selection.)

[Factory adjusted as 0 °C/min.]