n Recommended terminal

Use a solderless terminal with insulation sleeve to fit to M3 screw as shown below.












11.2 Wiring connection examples

Notices

• Use a thermocouple and compensating lead wire according to the input

specifications of this controller.

• Use a 3-wire RTD system according to the input specifications of this controller.
• This controller has no built-in power switch or fuse. It is necessary

to install them manually (IEC approved, 100 V AC 5 A or 220 V AC 5 A)
in the circuit near the external controller.

• In the case of 24 V DC, do not confuse the polarity.
• For the relay contact output type, use an external auxiliary electromagnetic

switch to protect the built-in relay contact.

• When wiring, keep the input wire (Thermocouple, RTD, etc.) away from AC

source and the load wire to avoid external interference.

• Use a thick wire (1.25 to 2.0 mm

2

) for the earth ground.

3.2mm

5.8mm or less

3.2mm

5.

8mm or less