Operating Instructions Temperature Indicating Controller CF1H

V 1.2

01/2007

- 72 -


<Indication>

Phenomenon

Presumed cause and the action





If indication
of PV display
is abnormal or
unstable.

• Designation of the Sensor input is improper.
Î Set the Sensor input properly by the Rotary switch

(SW303) and the DIP switch (SW304).
(page 10, 11)

• Temperature unit (°C or °F) is mistaken.
Î Set the unit properly by the DIP switch. (page 10)
• Sensor correcting value is unsuitable.
Î Set the value suitably. (page 23)
• Specification of the Thermocouple or RTD is improper.
• AC may be leaking into thermocouple or the RTD circuit.
• There may be an equipment producing an inductive

fault or noise near the controller.


<Key operation>

Phenomenon

Presumed cause and the action

If setting mode
cannot be selected.

• Manual control is selected.
Î

Change the mode to Automatic control (page 36)

If settings are
impossible.
If the value does
not change by the
, keys.

• Setting value lock (mode 1 or 2) is designated.
Î

Release the lock designation. (page 22)

• During PID auto-tuning.
Î

Cancel the tuning if necessary. (page 17)

If the setting
indication does not
change in the rated
scale range even if
the , keys
are pressed, and
setting is impossible.



• Main setting value high limit or low limit may be

set at the point the value does not change.

Î

Set it again by Auxiliary function setting mode 1.

If it does not start
even if the

OUT

/

OFF

key

is pressed in the
Program mode.


• Step time is not set.
Î

Set the step time. (page 35)