12. Specifications

12.1 Standard specifications

Mounting method

:

Flush

Setting

: Input system using membrane sheet key

Display

PV display

: Red LED display 4 digits, size, 8 (H) x 4 (W) mm

SV/MV/TIME display : Green LED display 4 digits, size, 8 (H) x 4 (W) mm

Setting value memory number (MEMO) display:

Yellow LED display 1 digit, size, 8 (H) x 4 (W) mm

Indicating accuracy

Thermocouple input : Within ±0.2 % of input range full scale ±1 digit

however, for R or S input, the range 0 … 200 °C (400 °F),
Within ±4 °C (8 °F)

When B input, the range 0 … 300 °C (600 °F),
Accuracy is not guaranteed.

When K, J, T input, range less than 0 °C (32 °F),
Within ±0.4 % of full scale ±1 digit
(Cold junction compensating accuracy, ±1 °C, at 0 … 50 °C)

RTD input

: Within ±0.2 % of input range full scale ±1 digit

Current input

: Within ±0.2 % of input range full scale ±1 digit

Voltage input

: Within ±0.2 % of input range full scale ±1 digit

Setting accuracy

: The same as indicating accuracy

Input sampling period

: 0.125 seconds

(In the case of the option EA0/EA4/EV0/EV1
or W12/W15/W32/W35 0.5 seconds)

Input

Thermocouple

: K, J, R, S, B, E, T [JIS, IEC], C (W/Re5-26) [ASTM],

N (IEC) and PL-ll (NBS)

External resistance, 100

Ω or less

In the case of input burnout, Upscale

RTD

: Pt100 (JIS, IEC), JPt100, 3-wire system

Allowable input lead wire resistance,

10

Ω or less per wire

In the case of input burnout, Upscale

Current

: 0 … 20 mA DC, 4 .. 20 mA DC

Input impedance, 50

Ω

Allowable input current, 100 mA or less

In the case of input burnout, 0 … 20 mA, the same as 0 mA

4 … 20 mA, Downscale

Voltage

: 0 … 1 V DC

Input impedance, 1 M

Ω or greater

Allowable input voltage, 5 V or less

Allowable signal source resistance, 2 k

Ω or less

In the case of input burnout, Upscale

Supply voltage

: 100 … 240 V AC 50/60 Hz, 24 V AC/DC 50/60 Hz

Allowable voltage fluctuation

:

100 … 240 V AC : 85 … 264 V AC

24 V AC/DC

: 20 … 28 V AC/DC

Advertising