Operating Instructions Temperature Indicating Controller CF1H

V 1.2

01/2007

- 65 -

Action

: ON/OFF action

Hysteresis setting range

When thermocouple or RTD input, 0.1 … 100.0 °C (°F)

When DC input, 1 … 1000

(Decimal point place follows the selection.)

Output

: Relay contact 1a

Control capacity, 250 V AC, 3 A (resistive load)

250 V AC, 1 A (inductive load cosø =0.4)

Circuit insulation configuration





















(*1) When both Main output and Cooling output are Current output type or

Non-contact voltage output type (the SSR drive), A to B is non-isolated.

(*2) When Main output is Current output type or Non-contact voltage output type

(the SSR drive), A to F and A to G are non-isolated.

When Cooling output is Current output type or Non-contact voltage output type

(the SSR drive), B to F and B to G are non-isolated.


Insulation resistance

10M

Ω or greater at 500Vdc

Insulation test must not be carried out between A-B in the case of Circuit
insulation configuration (*1), and between A-F, B-F, A-G, B-G, C-D-E and
F-G in the case of Circuit insulation configuration (*2) because they are
non-isolated.

Dielectric strength

Between input terminal and ground terminal, 1.5 kV AC for 1 minute
Between input terminal and power terminal, 1.5 kV AC for 1 minute
Between power terminal and ground terminal, 1.5 kV AC for 1 minute
Between output terminal and ground terminal, 1.5 kV AC for 1 minute
Between output terminal and power terminal, 1.5 kV AC for 1 minute

Ground terminal

Isolated

Power source

Main output

CPU

Communication part

Isolated

Cooling output,

Alarm 2 output or

Loop break alarm

output

Alarm 1 output

Isolated

Isolated

Heater burnout

alarm output

Isolated

Isolated

Isolated

Non-isolated

Input

CT input

External

setting

input

Transmission

output

Non-isolated

Setting value

memory number

external change

(*2)

(*1)

Isolated

Isolated

Isolated

(*2)

G

A

B

C

D

E

F