Setting value memory number external selection [SM7]

Selects the setting value memory number from 7 files (under mentioned data as one file) by external
terminal. (Main setting value, PID values, Cooling output proportional band setting value, Alarm 1 and 2
setting values, Overlap band or Dead band, Main output high limit, Main output low limit, Cooling output
high limit and Cooling output low limit)

Memory number 1 … 7 (7 files)
Data

12

External setting [EA or EV ]
Main setting value can be set by external analog signal.

Setting

signal

:

Current

0 … 20 mA DC [EA0]

4 … 20 mA DC [EA4]

Input

impedance

50

Ω (non-isolated with input)

:

Voltage

0 … 1 V DC [EV0]

1 … 5 V DC [EV1]

Allowable input voltage 5 V or less

Input impedance, 100 k

Ω (non-isolated with input)

Setting signal sampling period: 0.5 seconds

(If this function is applied, the input sampling period also will change to 0.5 seconds.)

Heater burnout alarm output [W12, W15, W32 or W35] (Including sensor burnout alarm)

Watches the heater current with CT (current transformer), and detects the
burnout. (This option cannot be applied to the type current output.)

Rating

: 20 A [Option W12, W32] or

50 A [Option W15, W35]

Setting range

: In the case of 20 A, 0.0 … 20.0 A (however, the indication is 0 … 50.0)

In the case of 50A, 0.0 … 50.0 A

(Setting the value to 0.0 disables the function.)

Setting accuracy : ±5 %
Action point

: Setting value

Action

: ON/OFF action

Output

: Relay contact 1a (No self-holding)

Control capacity, 250 V AC, 3 A (resistive load)

250 V AC, 1 A (inductive load, cosø=0.4)

Insulated power output [P24]

Can be used as a small capacity power source for each sensor and converter.
The insulated power output [P24] is not available with a combination of

Alarm 2 output (A2), Heating/Cooling control output [D 2] or Loop break

alarm output (LA).
Output 24 ±3 V DC (when the load current is 30 mA)

Ripple voltage, within 200 mV (when the load current is 30 mA)

Screw type mounting bracket [FS]

Mounting panel thickness is 1 … 15 mm.