Operating Instructions Temperature Indicating Controller CF1H

V 1.2

01/2007

- 27 -


PV filter time constant

Mode to suppress the PV fluctuation caused by

Setting

such as disturbance.

Setting value

Set the value larger by degrees, and find the setting

value at which the value does not fluctuate.

MODE

If the value is set too large, it affects control result

due to the delay of response.

Setting range: 0.0 … 10.0 s

[Factory adjusted as 0.0 s]

Main output high limit setting

Mode to set the high limit value of the main output.

Setting value

Setting range: Main output low limit value to 105 %

Setting greater than 100 % is effective to the type

MODE

Current output. [Factory adjusted as 100 %]

This display is not available for the ON/OFF action.

Main output low limit setting

Mode to set the low limit value of the main output.

Setting value

Setting range: –5 % to Main output high limit value

Setting less than 0 % is effective to the type Current output.

MODE

[Factory adjusted as 0 %]

This display is not available for the ON/OFF action.

Main output ON/OFF

Mode to set the ON/OFF action hysteresis of the

action hysteresis setting

main control output.

Setting value

Setting range: 0.1 … 100.0 °C

[Factory adjusted as 1.0 °C]

MODE

This display is indicated only when the ON/OFF action

is designated in Control action designation (page10).