(6) Program mode

In PV/SV display mode, if the key is pressed for approximately 3 seconds while the key is being
pressed, the Program mode can be selected.
The setting value can be increased or decreased by pressing the , and FAST keys.
If the MODE key is pressed, the setting value is registered and the next setting item is selected.

As to the setting values of the step 1 to 7, each setting value for setting value memory number 1 to 7 set
during the Fixed value control is assigned respectively. For example, values in memory number 1 are
assigned to the values for step 1, and number 2 for step 2.

If the Pattern end output is designated and the program control is performed, the Pattern end output is
turned on when the program is completed.

When the Pattern end output is on and if the

OUT

/

OFF

key is pressed, the Pattern end output is turned off. If the

OUT

/

OFF

key is pressed again, the program will be performed.

If some steps are unnecesary, set the times 00.00 for the step numbers not used.


Program Example

Step number (Setting
value memory number)

1 2 3 4 5 6 7

Main setting value

500

500

1000

1000

200

200

100

Proportional band

2.0

1.8

2.0 1.8 2.5 1.8 2.0

Integral

time

180 80 180 80 200 80 200

Derivative

time

30 20 30 20 50 20 50

Proportional

cycle

30 30 30 30 30 30 30

Alarm

1

2 5 2 5 10 0 5

Alarm

2

2 5 2 5 10 0 5

Step time

00:30 01:00 00:40 01:00 02:00 00:30 01:00