WIKA CF1H User Manual

Page 33

Advertising
background image

Operating Instructions Temperature Indicating Controller CF1H

V 1.2

01/2007

- 33 -


Output selection when

Mode to select the control output OFF or not when

input burnout

DC input is over scale or under scale.

Selected value

MODE

Control output OFF

Control output ON


[Factory adjusted as Control output

]

PV/SV display mode
Actual Main setting
temperature value




Energized/Deenergized function

[If the alarm action energized is selected]

When the alarm output action indicator is lit, the alarm output (terminal - , - ) is conducted (ON).
When the alarm output action indicator is unlit, the alarm output is not conducted (OFF).

[If the alarm action deenergized is selected]

When the alarm output action indicator is lit, the alarm output (terminal - , - ) is not
conducted (OFF). When the alarm output action indicator is unlit, the alarm output is conducted (ON).

Advertising