Operating Instructions Temperature Indicating Controller CF1H

V 1.2

01/2007

- 30 -


Alarm 1 (A1) action

Mode to set the action delayed timer for Alarm 1.

delayed timer setting

Setting range: 0 … 999 9s

Setting value

[Factory adjusted as 0 s]

Alarm output is turned on when the setting time has passed

MODE

after the input gets into the alarm output range.

This display is not indicated if the rotary switch is set to

No. 0 or No. 7 in Alarm 1 action designation (page 12).

Alarm 2 (A2) action

Mode to set the action delayed timer for Alarm 2.

delayed timer setting

Setting range: 0 … 9999 s

Setting value

[Factory adjusted as 0 s]

Alarm output is turned on when the setting time has passed

MODE

after the input gets into the alarm output range.

This display is not indicated when the option [2AS or 2AL] is not

applied and when the rotary switch is set to No. 0 or No. 7 in

Alarm 2 action designation even if the option [2AS or 2AL] is applied.

External setting input

Mode to set the high limit value of external setting input.

high limit setting

Setting value

(In the case of Option [EA4] (4 … 20 mA), the value

corresponds to 20 mA input.)

MODE

Setting range: External setting input low limit value

to Input range maximum value

[Factory adjusted as 400 °C]

This display is indicated only when the option

[EA0, EA4, EV0 or EV1] is applied.

External setting input

Mode to set the low limit value of external setting

low limit setting

input.

Setting value

(In the case of Option [EA4] (4 … 20 mA), the value

corresponds to 4 mA input.)

MODE

Setting range: Input range minimum value to

External setting input high limit value

[Factory adjusted as 0 °C]

This display is indicated only when the option

[EA0, EA4, EV0 or EV1] is applied.