SECTION 6 - JLG CONTROL SYSTEM

6-54

– JLG Lift –

3121284

DRIVE & BOOM PREVENTED –
PLATFORM OVERLOADED

827

The Platform is Overloaded and
Machine Setup

 LOAD SYSTEM = CUTOUT PLATFORM, Platform

Mode is active, and conditions of Table 6-6, Overload Variations
apply.
-or-
The Platform is Overloaded and Machine Setup

 LOAD SYSTEM =

CUTOUT ALL and conditions of Table 6-6, Overload Variations apply.

Refer to Table 6-6, Overload
Variations f
or machine
response.

Not all of the trigger conditions
are met

LIFT UP & TELE OUT PRE-
VENTED – PLATFORM OVER-
LOADED

828

MACHINE SETUP

 LOAD SYSTEM = SPECIAL 1

Platform Mode is active
The platform is Overloaded

Refer to Table 6-6, Overload
Variations f
or machine
response.

Not all of the trigger conditions
are met

LSS READING UNDER WEIGHT

8211

MACHINE SETUP

 LOAD SYSTEM NO

The load sensor has been calibrated and Gross Platform Weight <
(0.5 * Empty Platform Weight).

Ground Module to set Platform
Load State = Overloaded

Not all of the trigger conditions
are met

FRONT LEFT STEER VALVE –
OPEN CIRCUIT

8639

The Ground Module detects an open circuit at the Front Left Steer
Valve output.

Steer Left and Right speed are
limited to Creep

Cycle power to clear the fault.

FRONT LEFT STEER VALVE –
SHORT TO BATTERY

8640

The Ground Module detects a short to battery at the Front Left Steer
Valve output.

The Ground Module disables
the Drive Forward/Reverse and
Steer Left/Right outputs.

Cycle power to clear the fault.

FRONT LEFT STEER VALVE –
SHORT TO GROUND

8641

The Ground Module detects a short to ground at the Front Left Steer
Valve output.

The Ground Module disables
the Steer Left and Right out-
puts.

Cycle power to clear the fault.

FRONT RIGHT STEER VALVE –
OPEN CIRCUIT

8642

The Ground Module detects an open circuit at the Front Right Steer
Valve output.

Steer Left and Right speed is
limited to Creep

Cycle power to clear the fault.

FRONT RIGHT STEER VALVE –
SHORT TO BATTERY

8643

The Ground Module detects a short to battery at the Front Right Steer
Valve output.

The Ground Module disables
the Drive Forward/Reverse and
Steer Left/Right outputs

Cycle power to clear the fault.

FRONT RIGHT STEER VALVE –
SHORT TO GROUND

8644

The Ground Module detects a short to ground at the Front Right Steer
Valve output.

The Ground Module disables
the Steer Left and Right out-
puts

Cycle power to clear the fault.

OSCILLATING AXLE SWITCH
DISAGREEMENT

8669

The Ground Module detects that Oscillating Axle switch #1 and
switch #2 are not in agreement. Note: This fault will not to be
reported if DTC 23104 BOOM TRANSPORT SWITCH DISAGREEMENT is
active.

The Ground Module assumes
an Above Elevation State and
de-energizes J1-7 Oscillating
Axle output.

Cycle power to clear the fault.

LSS WATCHDOG RESET

991

The Ground Module detects an LSS report of an anomaly that has
caused a WatchDog Timer reset.

The Ground Module sets the
Platform Load State to Over-
loaded

Cycle power to clear the fault.

LSS EEPROM ERROR

992

The Ground Module detects an LSS report of an anomaly that exists in
the LSS EEPROM

The Ground Module sets the
Platform Load State to Over-
loaded

Cycle power to clear the fault.

LSS INTERNAL ERROR – PIN
EXCITATION

993

The Ground Module detects an LSS report of improper excitation
voltage.

The Ground Module sets the
Platform Load State to Over-
loaded

Cycle power to clear the fault.

Table 6-5. Fault Code Troubleshooting Information

Help Message

DTC

Condition Producing DTC

Control System Response or

Machine Condition

Corrective Action/

Operational Requirement

for Function Movement

and/or to Clear Fault