Part 2: INSTALLATION

2.11Electrical Tank Heat Connections (Electric heat only)

Perform the following steps to connect the incoming electrical power to the tank heat circuits

in the remote control cabinet.

Refer to Fig. 2.4 below, and Fig. 2.5, page 15.

WARNING:

The installation of electrical supplies and controls must conform to local codes or, in the

absence of local codes, the National Electrical Code and good trade practices.

WARNING:

Dangerous voltages are present at the local electrical distribution system.

Dangerous voltages are present at the dishwasher when it is connected to the

local electrical distribution system.

WARNING:

When working on the dishwasher, disconnect the electric service and place a red tag at the

disconnect switch to indicate work is being done on that circuit.

1. Connect the incoming 440V/60/3PH power supply to the heat contactor marked for the

wash tank heater circuit. Refer to Part 1.5, Electrical Power Requirements, page 4,

for full load amp ratings.

2. Connect the incoming 440V/60/3PH power supply to the heat contactor marked for the

wash tank heater circuit. Refer to Part 1.5, Electrical Power Requirements, page 4,

for full load amp ratings.

3. Item A, Figure 2.5, page 15,

illustrates the incoming power

connections to the remote

control cabinet. Connections

are shown entering the top of

the cabinet, but the installer

may choose to route connections

to a different location if necessary.

4. Items B and C, Figure 2.5,

page 15, illustrate the conduit

routing from the remote control

cabinet to the tank heater junction

boxes located on the front of the

dishwasher.

5. Beginning with serial number

J1872, connect the tank heater

to the terminal block as shown in

in the Interconnection Drawings

located on page xxx in the back of

the manual.

Figure 2.4

Remote Control Cabinet

Incoming Power Connections

for Tank Heat Circuit

CONTROL

TRANSFORMER

POWER

TERMINAL BLOCK

3MOL

2MOL

MOT

OR OVERLOADS

1MOL

2M

1M

RINSE

W

ASH

DRIVE

W

ASH

DRIVE

GROUND

120V

120V

MACHINE ELECTRICAL

CONNECTION PLATE

POWER RINSE

TANK

HEAT CIRCUIT

WASH TANK

HEAT CIRCUIT

2

1