10 Technical data
104
2012-12-31/00561073 [SCR power switch TYA202]
10.3 Analog inputs (master only)
10.4 Analog output (actual value output master only)
10.4.1Display and measuring accuracy
All specifications refer to the controller nominal data.
10.5 Binary inputs
10.6 Binary output (fault signal output master only)
Current
0 (4) to 20 mA R
i
= 50
Ω
Voltage
0 (2) to 10 V R
i
= 25 k
Ω
0 (1) to 5 V R
i
= 25 k
Ω
Analog output
Switched off as standard.
I
max
= 20 mA for standard signal voltage: 0 to 10 V, 2 to 10 V, 0 to 5 V
up to 1 to 5 V.
Burden max. 500
Ω
for standard signal current: 0 to 20 mA up to
4 to 20 mA
Depending on the device type, various internal measured variables
such as load current, load voltage or power can be output.
Supply voltage: ±2.5 %
Load current: ±1 %
Load voltage:
±1 % Power:
±2 %
Analog input
voltage/current: ±1 %
Analog output
voltage/current: ±1 %
Load resistance: ±2 %
(for resistive load)
12
11
+
–
Binary input 1
For connection to potential-free contact
Binary input 2
Relay (changeover contact)
without contact suppression
150,000 switching operations at a contact rating of 3 A/230 V 50 Hz (resis-
tive load)
Optocoupler output
I
Cmax
= 2 mA, U
CEOmax
= 32 V