2 Installation

2.1.2 Filtering and interference suppression

To prevent radio-frequency interference, such as occurs with a soft start in
phase angle control, electrical apparatus and systems must have interference
suppression implemented.

The control electronics of the SCR power controller correspond to the EMC re-
quirements of EN 61326.

However, electrical modules such as SCR power controllers do not have any
purpose by themselves. They provide a function as part of a complete system
or installation.
Where applicable, the entire load circuit of the power controller must also have
suitable interference suppression filters fitted by the system provider.

There are a number of specialist companies that provide appropriate ranges of
filters to deal with any interference problems. Such filters are normally sup-
plied as complete modules that are ready to be connected.

2.1.3 Permissible load current depending

on the ambient temperature and the installation height

Ambient tem-
perature

45

50

60

75

20

200

T/°C

150

Load current in A

Reduction at a temperature of 45 °C:
2 %/kelvin

70 %

250

100

50