9 monitoring of the supply voltage drop, 10 firing-pulse inhibit, Monitoring of the supply voltage drop – JUMO 709062 TYA 202 - Three-Phase Power Controller Operating Manual User Manual

Page 85: Firing-pulse inhibit, 6 special device functions

Advertising
background image

2012-12-31/00561073 [SCR power switch TYA202]

83

6 Special device functions

6.9 Monitoring of the supply voltage drop

If the effective values of the analyzed half-waves are more than 10 % apart, an
alarm message is displayed and the binary output for the collective alarm
switches depending on the set control direction.

Immediate firing-pulse inhibit prevents the connected transformer loads from
destroying the semi-conductor fuses due to a DC component.
If there are no further supply voltage drops, the firing-pulse inhibit is removed
and the power controller continues operation (e.g. with a soft start).

Factory setting

Monitoring is not activated.

v Chapter 5.1.5 "Monitoring"

6.10 Firing-pulse inhibit

The inhibit function serves to protect the SCR power controller and the con-
nected devices.

Internal

The SCR output is locked during:

- Device switch-on (during the startup procedure)

- Reset or restart as a result of changes in the configuration level

- Insufficient or excessive supply voltage

- Master/slave data line interruption

- Master/slave synchronization failure

- Setup of data transfer to the device

- Device temperature greater than 115 °C

- Rotary electrical field error

- Short-term supply drops > 10 % within a half-wave

v Chapter 6.9 "Monitoring of the supply voltage drop"

External

Via the "Inhibit" binary input

v Chapter 3.3 "Connection diagram"

Alternatively, the SCR output can also be switched off via the PROFIBUS,
RS422/485 interfaces.

Advertising