10 Technical data

106

2012-12-31/00561073 [SCR power switch TYA202]

Fans (only for
type 709062/X-0X-250...)

Depending on the load voltage of the power controller, the fan terminal X14
must be supplied with the voltage specified below.
The lead protection must be between 2 A and a maximum of 5 A.
The fan is temperature-controlled, switches on automatically when the de-
vice temperature reaches 85 °C, and remains in operation until the device
temperature falls below 70 °C.

Resistance to climatic condi-
tions

Rel. humidity

85 % annual average, no condensation 3K3 according to

EN 60721

Installation position

Vertical

Test voltage

According to EN 50178 Tab. 18

Creepage distances

8 mm between supply current circuit and SELV circuits
For type 709062/X -0X-020...
12.7 mm between supply current circuit and SELV circuits
From type 709062/X -0X-032...
SELV = Separate Extra Low Voltage (safe low voltage)

Case

Plastic, flammability class UL94 V0, color: cobalt blue RAL 5013

Power dissipation

The power dissipation can be calculated using the following empirical for-
mula:
P

v

= 2x (20W + 1.3V x I

Load

A)

Maximum temperature of the
cooling body

110 °C

Weight

Load current 20 A approx. 2.2 kg
Load current 32 A approx. 4.2 kg
Load current 50 A approx. 5.4 kg
Load current 100 A approx. 7.6 kg
Load current 150 A approx. 17 kg
Load current 200 A approx. 19 kg
Load current 250 A approx. 20.4 kg

Standard accessories

1 Operating Manual B 709062.0

Load voltage of the power

controller

Tolerances

Fan specifications

Load voltage AC 24 V

-20 to +15 %, 45 to 63 Hz

AC 24 V/30 VA

Load voltage AC 42 V

-20 to +15 %, 45 to 63 Hz

Load voltage AC 115 V

-15 to +6 %, 45 to 63 Hz

AC 115 V/30 VA

Load voltage AC 230 V

-15 to +6 %, 45 to 63 Hz

AC 230 V/30 VA

Load voltage AC 265 V

Load voltage AC 400 V

Load voltage AC 460 V

Load voltage AC 500 V