10 technical data – JUMO 709062 TYA 202 - Three-Phase Power Controller Operating Manual User Manual
Page 108

10 Technical data
106
2012-12-31/00561073 [SCR power switch TYA202]
Fans (only for
type 709062/X-0X-250...)
Depending on the load voltage of the power controller, the fan terminal X14
must be supplied with the voltage specified below.
The lead protection must be between 2 A and a maximum of 5 A.
The fan is temperature-controlled, switches on automatically when the de-
vice temperature reaches 85 °C, and remains in operation until the device
temperature falls below 70 °C.
Resistance to climatic condi-
tions
Rel. humidity
≤
85 % annual average, no condensation 3K3 according to
EN 60721
Installation position
Vertical
Test voltage
According to EN 50178 Tab. 18
Creepage distances
8 mm between supply current circuit and SELV circuits
For type 709062/X -0X-020...
12.7 mm between supply current circuit and SELV circuits
From type 709062/X -0X-032...
SELV = Separate Extra Low Voltage (safe low voltage)
Case
Plastic, flammability class UL94 V0, color: cobalt blue RAL 5013
Power dissipation
The power dissipation can be calculated using the following empirical for-
mula:
P
v
= 2x (20W + 1.3V x I
Load
A)
Maximum temperature of the
cooling body
110 °C
Weight
Load current 20 A approx. 2.2 kg
Load current 32 A approx. 4.2 kg
Load current 50 A approx. 5.4 kg
Load current 100 A approx. 7.6 kg
Load current 150 A approx. 17 kg
Load current 200 A approx. 19 kg
Load current 250 A approx. 20.4 kg
Standard accessories
1 Operating Manual B 709062.0
Load voltage of the power
controller
Tolerances
Fan specifications
Load voltage AC 24 V
-20 to +15 %, 45 to 63 Hz
AC 24 V/30 VA
Load voltage AC 42 V
-20 to +15 %, 45 to 63 Hz
Load voltage AC 115 V
-15 to +6 %, 45 to 63 Hz
AC 115 V/30 VA
Load voltage AC 230 V
-15 to +6 %, 45 to 63 Hz
AC 230 V/30 VA
Load voltage AC 265 V
Load voltage AC 400 V
Load voltage AC 460 V
Load voltage AC 500 V