Subordinate control loop, 5 configuration – JUMO 709062 TYA 202 - Three-Phase Power Controller Operating Manual User Manual

Page 53

Advertising
background image

2012-12-31/00561073 [SCR power switch TYA202]

51

5 Configuration

Subordinate control
loop

U

2

, U, I

2

, I, P

Note:
The subordinate control loop only appears for:

Power controller

r

SCR control

r

Continuous (control-

ler).

Subordinate control loops are used to eliminate or compen-
sate for external disturbances, such as mains voltage fluctua-
tions and changes in load resistance that would have a
negative effect on the control loop.

The U setting is used when the load voltage should be directly
proportional to the default setpoint value.
The I setting is used when the load current should be directly
proportional to the default setpoint value.

The following subordinate control loops have proven advanta-
geous for heating elements that do not have a linear tempera-
ture behavior or are subject to aging:
U

2

is used for:

- Positive temperature coefficient, molybdenum disilicide
- If

R

is constant

- Brightness controls

I

2

is used for:

- Negative temperature coefficient (TC)

P is used for:
- Temperature-dependent temperature coefficient
- Free-running economy circuit
- General applications
- SIC load with automatic aging compensation

Switched off

The diagram shows how the phase angle is specified via a
standard signal without a subordinate control loop.

Value / settings

Description

k

/ bold = factory setting

Phase angle α

0 to 20 mA
0 to 10 V

Analog input