6 Special device functions

68

2012-12-31/00561073 [SCR power switch TYA202]

For heating elements with a temperature coefficient TC

1 the limit value can

be taken directly from the following tables:

Undercurrent

The specifications in % refer to load current changes

Overcurrent

The specifications in % refer to load current changes

Number of
heating elements

Star connection with sepa-
rate star points without neu-
tral conductor

Star connection with com-
mon star points without
neutral conductor

Delta connection

5

10 %

-

-

4

13 %

10 %

-

3

17 %

13 %

10 %

2

25 %

20 %

12 %

1

50 %

50 %

21 %

Example:
2 heating
elements

L3

L2

L1

L3

L2

L1

L3

L2

L1

Number of
heating elements

Star connection without neutral
conductor

Delta connection

6

-

-

5

10 %

-

4

10 %

10 %

3

14 %

13 %

2

25 %

26%

Example for 2
heating elements

L3

L2

L1

L3

L2

L1

H

As a general rule, load monitoring does not yet take place during the soft start
phase (which can last for longer due to active current limiting) as the standard
operating range of the load has not yet been reached.Teach-In cannot yet be per-
formed in this phase either.