7 general characteristic data, General characteristic data, 10 technical data – JUMO 709062 TYA 202 - Three-Phase Power Controller Operating Manual User Manual

Page 107

Advertising
background image

2012-12-31/00561073 [SCR power switch TYA202]

105

10 Technical data

10.7 General characteristic data

SCR control:

Setpoint specification
current input
(can carry current up to
25 mA)

Setpoint specification
voltage input
(surge proof up to max. DC 32 V)

Setpoint specification
Binary input1, 2
(surge proof up to max. DC 32 V)

Via inter-
face

Continuous

The power controller provides the power for the load contin-
uously depending on the configured default setpoint value.

-

Possible

Logic
(Solid state relay SSR)

The power controller acts like a switch and switches the load
ON and OFF. The switching threshold is always in the middle
of the set current/voltage range
For 4 to 20 mA, it is 12 mA; for 0 to 10 V, it is 5 V.

OFF logical "0" = 0 to +0.8 V;
ON logical "1" = +2 to 3.3 V

Possible

Circuit options

- Three-phase economy circuit in master slave operation

Operating modes

- Burst-firing operation for resistive or transformer load

Special features

- Dual energy management
- Soft start with pulse groups

Subordinate control loop

U² control as standard
Can be switched over to U, I, I², P control depending on device type

Electrical connection

For type 709062/X -0X-020...
Control and load leads are connected via screw terminals.
From type 709062/X -0X-032...
Control leads are connected via screw terminals and load leads via cable
lugs DIN 46235 and DIN 46234 or tubular cable lugs.

Operating conditions

The power controller is designed as a panel-mounting device according to:
EN 50178, pollution degree 2, overvoltage category Ü III

Electromagnetic
compatibility

According to DIN 61326-1
Emitted interference: Class B
Interference resistance: industrial requirements

Protection class

All device types IP20 according to EN 60529

Protection rating

Protection rating I, with isolated control circuitry for connection to SELV cir-
cuits

Permissible
ambient temperature range

40 °C with forced air cooling using fan for type 709062/X-0X-250...
0 to 45 °C with natural air cooling (extended temperature range class 3K3
according to EN 60721-3-3)
At higher temperatures, operation with reduced type current is possible.
(from 45 °C with type current -2 % / °C)
v Chapter 2.1.3 "Permissible load current depending on the ambient tem-

perature and the installation height"

Permissible storage
temperature range

-30 to +70 °C (1K5 according to EN 60721-3-1)

Cooling

- Natural convection up to a load current of 200 A
- From 250 A of load current, forced convection
- At installation heights over 1000 m, the current carrying capacity of the
power controller decreases
v Chapter 2.1.3 "Permissible load current depending on the ambient tem-

perature and the installation height"

Advertising