3 setpoint value configuration, Setpoint value configuration, 4 operation – JUMO 709062 TYA 202 - Three-Phase Power Controller Operating Manual User Manual
Page 47

2012-12-31/00561073 [SCR power switch TYA202]
45
4 Operation
4.2.3 Setpoint value configuration
Current load current
10 % to max. load
current for the de-
vice type +10 %
Current limiting:
It is possible to modify the current limit value in phase angle
control mode during operation.
The current is limited in the master branch.
This window is not displayed if "Current limiting" is set to "no"
in the configuration.
Current resistance
0 to 999.99
Ω
Resistance limitation:
Indirect temperature limit for a heating element with positive
temperature coefficients.
The resistance value is measured in the master branch.
Resistance cannot be measured directly in the three-phase
current economy circuit. However, the current resistance mea-
sured at an operating point can be used as a resistance limit
value.
v Chapter 5.1.2 "Power controller"
v Chapter 6.6 "Resistance limitation (R control)"
k
/ bold = factory setting
Value range
Description
Current load voltage
0 to U
nom.
to 1.15 U
n-
om.
of the load voltage,
0 to P
nom.
to 1.15 P
nom.
of the power
0 to I
nom.
of the max. load current
0 to 100 %
of the output level
In the case of continuous SCR control via the analog input,
the maximum actuating variable at the measuring range end
(e.g. 20 mA) can be varied during operation.
The measured values in the master branch are measured.
The displayed value depends on the "Subordinate control
loop" setting:
U
2
and U: display in V (example: 0 to 400 to 460 V)
P: display in kW (example: 0 to 8.00 to 9.20 kW)
I
2
and I: display in A (example: 0 to 20 A)
None: display in % (example: 0 to 100 %)
Current load voltage
0 to U
nom.
of the load voltage,
0 to P
nom.
of the power
0 to I
nom.
of the max. load current
0 to 100 %
of the output level
In the case of continuous SCR control via the analog input,
the base load at the measuring range start (e.g. 0 mA) can
be varied during operation.
The measured values in the master branch are measured.
The displayed value depends on the "Subordinate control
loop" setting.
k
/ bold = factory setting