4 Operation

46

2012-12-31/00561073 [SCR power switch TYA202]

4.2.4 Monitoring

The value to be monitored can be adjusted.

v Chapter 5.1.5 "Monitoring"

The load voltage was used in this example.

Value range

Your setting:

Current measured
value

0 to 9999.9

The absolute minimum limit value for load voltage, load cur-
rent, power, resistance, supply voltage, or device temperature
can be monitored.
The measured values in the master branch are measured.

v Chapter 5.1.5 "Monitoring"

Example:
If the voltage falls below 20 V, an alarm is issued.

Current measured
value

0 to 9999.9

The absolute maximum limit value of load voltage, load cur-
rent, power, resistance, supply voltage, or device temperature
can be monitored.
The measured values in the master branch are measured

v Chapter 5.1.5 "Monitoring"

Example:
If the voltage exceeds 100 V, an alarm is issued.

0 to 1 to 9999.9

The switching differential at the minimum or maximum limit
value

Current deviation
from teach-in
(i.e. if it exceeds 0 %)
the load has become
high-impedance;
if it is below 0 %,
the load has become
low-impedance

0 to 10 to 100 %

Partial load failure or partial load short circuit:

The monitoring value for the percentage modification of the
load is set (undercurrent or overcurrent).

v Chapter 5.1.5 "Monitoring"

By displaying the current deviations in all three phases of the-
Teach-In value, it is possible to check how, for example, the
resistance change behaves over the entire operating range.
The load monitoring limit value can then be adjusted accord-
ingly.
Guide values for the identification of load errors:

v Chapter 6.1 "Detection of load faults"