9 what to do, if, What to do, if, Chapter 9 "what to do, if – JUMO 709061 TYA 201 - Single-Phase Power Controller Operating Manual User Manual

Page 105

Advertising
background image

2012-12-01/00561071 [SCR Power Controller TYA201]

103

9 What to do, if ...

What is happening?

Cause/remedy

Information

Green Power LED is
flashing

- Display switch-off active

h Press any key

v Chapter 5.1.1

"Device data"

Power controller is not
producing power even
though the green Power
LED
is lit and a setpoint value
has been set.

- Parameters have been changed in the

configuration level but not completed.

h Leave the configuration level by pressing

EXIT and wait for a restart.

-

- Wire break at the analog input or incor-

rect analog input wiring

v Chapter 3.3

"Connection dia-
gram"

- Setpoint value configuration incorrectly

configured, e.g. set via interface.

v Chapter 5.1.4

"Setpoint value
configuration"

- Input for firing-pulse inhibit active

A padlock symbol is shown in the info line
as the operating mode.

Undo connection between screw terminal 7
and 8 at terminal X2_2.

v Chapter 4.1.2

"Displaying mea-
sured values"

- Load break

h Check load and load connections

v Chapter 8 "Fault

messages and
alarms"

Fuse LED is lit

- Semi-conductor fuse defective due to

short circuit in power section

h Remedy short circuit in the load or load

circuit

h Fit a new semi-conductor fuse

v Chapter 8.2 "Re-

placing a defective
semi-conductor
fuse"

Power controller is pro-
ducing power even
though no setpoint value
(output level) is specified
by the controller.

- Configuration problem:

Controller output signal set to 4 to 20 mA
and analog input current on power con-
troller set to 0 to 20 mA.

h Check configuration and set same stan-

dard signals at the controller and power
controller.

v Chapter 5.1.3

"Analog inputs"

v Chapter 5.1.4

"Setpoint value
configuration"

- Power controller in manual mode

h Exit manual mode by pressing EXIT

v Chapter 6.2

"Manual mode"

- Base load default value set

h Check settings for base load default val-

ue

v See "Base load"

on page 60.

- SCR short circuit

v Chapter 8 "Fault

messages and
alarms"