2012-12-01/00561071 [SCR Power Controller TYA201]

55

5 Configuration

Cycle time

Fixed (500 ms)

(For slow heating ele-
ments)

Note:
This setting is only available in burst-firing mode.

For example, for a fixed period of 500 ms, 5 sine waves are
switched on and 20 switched off at an output level of 20 %.

Fastest possible

(For quick-response
heating elements)

With this setting, the cycle time is variable. At the required out-
put level, the device attempts to find the shortest possible cy-
cle time for entire sine wave cycles. At an output level of 20 %,
this relates to one sine wave ON and four sine waves OFF.

Min. ON period

None
3 full sine waves

Dependent on the cycle time setting.

At least 3 full sine waves are always let through.

At an output level of 50 % and fastest possible cycle time,
3 sine waves are switched on and 3 switched off.

Note:
Particularly suitable for the control of transformer loads

α

start

No

Note:
This setting is available in continuous burst-firing mode and in
logic operation.

No: for resistive load
Yes: for transformer loads

If set to "Yes", the first half-wave of each pulse group is cut
with the set phase control angle

α

.

Yes

Angle

α

start

0 to 70 to 90 °el

Phase control angle for

α

start

Soft start

No

This setting determines the starting behavior of the power
controller after power ON and is deactivated ex works.

Value/settings

Description

k

/ bold = factory setting

u

t

500ms

5

20

u

t

500ms

5

20

u

t

u

t

a

a