8 fault messages and alarms – JUMO 709061 TYA 201 - Single-Phase Power Controller Operating Manual User Manual
Page 98

8 Fault messages and alarms
96
2012-12-01/00561071 [SCR Power Controller TYA201]
Slave: Attention!
High temp.
Device temperature is higher than 100 °C
(excess temperature)
- Ensure adequate ventilation or
provide for additional cooling
- Reduce load current
- Use power controller with high-
er maximum load current
Slave: Limit.
active high temp.
Device temperature is higher than 105 °C.
Device too hot!
Output level is reduced.
(limited power due to excess temperature)
- Ensure adequate ventilation or
provide for additional cooling
- Reduce load current
- Use power controller with high-
er maximum load current
Slave: Supply volt.
too low
Supply voltage is not within specified toler-
ance range
v Chapter 10.1 "Voltage supply, load
Check nominal voltage of the device
type
Slave: Supply volt.
too high
Supply voltage is not within specified toler-
ance range
v Chapter 10.1 "Voltage supply, load
Check nominal voltage of the device
type
Slave: Temp.
drop in supply
Dangerous temporary equal proportion for
transformer loads has been detected.
Ensure stable mains supply.
Inhibit by
inhibit input
A firing-pulse inhibit has been triggered via
a potential-free contact.
No power from the power controller.
v Chapter 3.3 "Connection dia-
Open contact between terminal 7 and
8 at screw terminal X_2.
Inhibit by
ext. inhibit
The firing-pulse inhibit has been triggered
via an interface.
v Interface manual "Ext. inhibit"
Soft start phase
This message appears in the display until
the soft start has been completed.
v Chapter 5.1.2 "Power controller"
Current limiting
active
The required output level causes an exces-
sive load current and is therefore limited to
the set value.
v Chapter 5.1.2 "Power controller"
Resistance
limitation active
The desired output level leads to current/
voltage values that exceed the set load re-
sistance. The output level is limited to the
permissible resistance to prevent overheat-
ing.
v Chapter 5.1.2 "Power controller"
Fault message
Cause
Remedy