5 Configuration

54

2012-12-01/00561071 [SCR Power Controller TYA201]

Subordinate control
loop

U

2

, U, I

2

, I, P

Note:
The subordinate control loop only appears for:

Power controller

r

SCR control

r

Continuous (control-

ler).

Subordinate control loops are used to eliminate or compen-
sate external
disturbances, such as fluctuations in the supply voltage and
changes in load resistance, which would have a negative ef-
fect on the control loop.

The U setting is used when the load voltage should be directly
proportional to the default setpoint value.
The I setting is used when the load current should be directly
proportional to the default setpoint value.

The following subordinate control loops have proven advanta-
geous for heating elements that do not have a linear tempera-
ture behavior or are subject to aging:
U

2

is used for:

- Positive temperature coefficient, molybdenum disilicide
- If

R

is constant

- Brightness controls

I

2

is used for:

- Negative temperature coefficient (TC)

P is used for:
- Temperature-dependent temperature coefficient
- Free-running economy circuit
- General applications
- SIC load with automatic aging compensation

Switched off

The diagram shows how the phase angle is specified via a
standard signal without a subordinate control loop.

Value/settings

Description

k

/ bold = factory setting

Phase angle α

0 to 20 mA
0 to 10 V

Analog input