5 Configuration

60

2012-12-01/00561071 [SCR Power Controller TYA201]

Input in the event of
an error

Current, voltage, and interface input are monitored for errors
(wire breaks or bus errors). This setting specifies which alter-
native value the power controller should use if the default set-
point value is incorrect.
The last valid value is used ex works.

Last value
Voltage input or cur-
rent input

If, for example, an error (e.g. wire break) now occurs at the
current input, which is set ex works for the default setpoint
value, the power controller uses the value at the voltage input.

Value, adjustable

This means that the "Value in the event of an error" is used.

Value in the event
of an error

000.0

This value is used in the event of an error.

Maximum
actuating variable

0 to U

nom.

to 1.15 U

n-

om.

of the load voltage,
0 to P

nom.

to 1.15

P

nom.

of the power

0 to I

nom.

of the max. load cur-
rent
0 to 100 %
of the output level

In the case of continuous SCR control via the analog input,
the maximum actuating variable at the measuring range end
(e.g. 20 mA) can be varied during operation.

Note:
This setting is only available if power controller

r

SCR control

r

Continuous (power controller) is set.

The unit depends on the setting for subordinate control loop
and device type:
- U

2

and U: display in V (example: 0 to 230 to 264.5 V)

- P: display in W (example: 0 to 4600 to 5290 W)

- I

2

and I: display in A (example: 0 to 20 A)

- None: display in % (example: 0 to 100 %)

Base load

0 to U

nom.

of the load voltage,
0 to P

nom.

of the power

0 to I

nom.

of the max. load cur-
rent
0 to 100 %
of the output level

Note:
This setting is only available if power controller

r

SCR control

r

Continuous (power controller) is set.

The unit depends on the setting for subordinate control loop
and device type:
- For voltage: 0 to 100 % of the max. load voltage (e.g. 0 V)
- For current: 0 to 100 % of the max. load current (e.g.
0 A)
- For power: 0 to 100 % of the power (e.g. 0 W)
- None: 0 to 100 % of the output level (e.g. 0 %)

v Chapter 1.3 "Order details"

k

/ bold = factory setting

Control signal

P

Base load: 680 W

Maximum
Output level: 3680 W

0 mA

20 mA

3000W

0...20mA

־

Base load