8 Fault messages and alarms

94

2012-12-01/00561071 [SCR Power Controller TYA201]

Attention!
High temperature

Device temperature is higher than 100 °C
(excess temperature)

- Ensure adequate ventilation or

provide for additional cooling

- Reduce load current

- Use power controller with high-

er maximum load current

Limiting active
high temperature

Device temperature is higher than 105 °C .
Device is too hot, output level is reduced!
(limited power due to excess temperature)

- Ensure adequate ventilation or

provide for additional cooling

- Reduce load current

- Use power controller with high-

er maximum load current

Supply voltage is
too low

Supply voltage is not within specified toler-
ance range

v Chapter 10.1 "Voltage supply, load

current"

Check nominal voltage of the device
type

v Chapter 1.3 "Order details"

Supply voltage is
too high

Supply voltage is not within specified toler-
ance range

Chapter 10.1 "Voltage supply, load cur-
rent"

Check nominal voltage of the device
type

Chapter 1.3 "Order details"

Temporary
drop in supply

Dangerous temporary equal proportion for
transformer loads has been detected.

v Chapter 5.1.5 "Monitoring"

Ensure stable mains supply.

Master-slave
rotary field error

Counterclockwise rotary field has been de-
tected

v Chapter 3.3.6 "Master-slave

three-phase current economy
circuit for resistive loads in star,
delta connection, or transformer
loads (resistive-inductive)"

Master-slave
incorrectly wired.

Wiring fault has been detected

Rotary field detec-
tion
failed

Rotary field detection not possible

- Check connection

v Chapter 3.3 "Connection dia-

gram"

- Eliminate line disturbances

Wire break
Current input

Input current too small for the set measur-
ing range.

- Check wiring for wire breaks and

reverse polarity.

- Check upstream devices (con-

trollers)

Wire break
Voltage input

Input voltage too small for the set measur-
ing range.

- Check wiring for wire breaks and

reverse polarity.

- Check upstream devices (con-

trollers)

Malfunction
Bus error

No connection to the Profibus master

Check wiring and master device (PLC).

Master-slave
Error in comm.

Error in the data transfer between master
and slave

Is the patch cable plug connected cor-
rectly?

Fault message

Cause

Remedy