7 binary output, Binary output, 5 configuration – JUMO 709061 TYA 201 - Single-Phase Power Controller Operating Manual User Manual
Page 67

2012-12-01/00561071 [SCR Power Controller TYA201]
65
5 Configuration
5.1.7
Binary output
This parameter specifies which control direction the binary output should have. It is
controlled by the multi-input interference signal.
v Chapter 8.1 "Binary signal for collective fault"
h
Switch to the configuration level
r
Binary output using the
key
Value/settings
Description
Control direction,
binary output
N/O contact
No fault message present:
14 and 15 pole and N/C contact closed or
13 and 15 optocoupler collector-emitter loop high-impedance
Fault message present:
13 and 15 pole and N/O contact closed or
13 and 15 optocoupler collector-emitter loop low-impedance
N/C contact
No fault message present:
13 and 15 pole and N/O contact closed or
13 and 15 optocoupler collector-emitter loop low-impedance
Fault message present:
14 and 15 pole and N/C contact closed or
13 and 15 optocoupler collector-emitter loop high-impedance
k
/ bold = factory setting
13
14
15
E
S
C
Ö
P
Optocoupler
Relay
13
14
15
E
S
Optocoupler
Relay
C
Ö
P
13
14
15
E
S
Optocoupler
Relay
C
Ö
P
13
14
15
E
S
C
Ö
P
Optocoupler
Relay