5 Configuration

62

2012-12-01/00561071 [SCR Power Controller TYA201]

Limit value hystere-
sis

0 to 1 to 9999.9

Switching differential at the upper and lower limit of the moni-
toring range

Load monitoring

None

The load is not monitored.

Undercurrent

Note:
This parameter is only available if the device type is equipped
with an I, I

2

, or P subordinate control loop and current mea-

surement can therefore be performed.

v Chapter 6.1 "Detection of load faults"

Overcurrent

Note:
This setting is only available if load monitoring has been set
to under- or overcurrent.

Limit value load
monitoring

0 to 10 to 100 %

Partial load failure or partial load short circuit:
This setting specifies the percentage by which the load resis-
tance must have decreased or increased for a load error to be
triggered.

Load type load
monitoring

Standard

Default setting (suitable for most load types)

Infrared radiator
(short-wave)

Especially suitable for short-wave infrared radiators

Teach-in type load
monitoring

Automatic, once

The teach-in value is automatically determined once after
each power ON.

v Chapter 6.1.1 "Teach-in"

Manual

Teach-in can be performed in manual mode or at the opera-
tor level
.

v Chapter 6.2.2 "Configuring the teach-in (prerequisite

for teach-in in manual mode)"

v Chapter 4.2.4 "Monitoring"

Automatic, cyclical

Teach-in is performed cyclically at a time interval of 1 minute.

Mains voltage drop
monitoring

No

No monitoring

Yes

If the effective values of the analyzed half-waves are more
than 10 % apart, an alarm message is displayed and the bina-
ry output for the collective alarm switches depending on the
set control direction.
Immediate firing-pulse inhibit prevents the connected trans-
former loads from destroying the semi-conductor fuse due to
a DC component.
If there are no further supply voltage drops, the firing-pulse in-
hibit is removed and the power controller continues operation,
e.g. with a soft start.

k

/ bold = factory setting