8 Fault messages and alarms

Data cable
faulty

Communication between master and slave
interrupted.

Check the patch cable and replace, if
necessary

Synchronization
failed

Slave device switched off or communica-
tion between master and slave interrupted

Check plug connection of patch cable
or voltage supply

M/S incompatible
#0002...0008

- Master and slave are incompatible

- Different power controller types

used (max. load current, load volt-
age and subordinate control loop (if
applicable) do not match)

Use same power controller types with
same software versions.

#0002

Different device software versions

Update devices to same device soft-
ware versions

v Service hotline

#0003

VDN numbers of devices do not match

Master/slave operation not possible

#0006

Different nominal voltages (device types) of
master and slave device.

Master/slave operation not possible

v Chapter 1.3 "Order details"

#0007

Different nominal currents (device types) of
master and slave device.

#0008

Set subordinate control loop of the master
is not compatible with that of the slave de-
vice.

Change subordinate control loops of
both devices to U or U

2

.

Teach-in
load monitoring!

Reminder that "manual" teach-in has been
configured but not yet executed.

Perform teach-in

v Chapter 6.1 "Detection of load

faults"

Slave: Limit value
Min. value reached

The value has gone below the set limit val-
ue for the min. alarm at the slave

Check why the value has gone below
the limit value.

Slave: Limit value
Max. value reached

The set limit value for the max. alarm has
been exceeded at the slave

Check why the limit value has been ex-
ceeded.

Slave: Fault at
connected load

Break or short-circuit of a load resistor.

v Chapter 6.1 "Detection of load

faults"

Replace defective heating elements.

Slave:
Blown fuse
(red LED fuse is lit)

1. Semi-conductor fuse defective

v Chapter 8.2 "Replacing a defec-

tive semi-conductor fuse"

2. No voltage at terminal U1

- Check wiring

- Check the line fuse for the load

circuit

Slave:
SCR breakage

SCR defective

The device must be returned to JUMO
for repair.

h Return the device

Slave: SCR
short circuit

SCR defective

The device must be returned to JUMO
for repair.

h Return the device

Fault message

Cause

Remedy